PD Pico

노비코이엔지만의 전문적인 기술을 바탕으로 안전하고 신뢰할 수 있는 전력 시스템을 제공합니다.

PD Pico

TECHNICAL SPECIFICATIONS

Partial discharge measuring & othersFunction generator & others
Partial discharge measuring channels
Input connectorBNC female
Input impedance1MΩ
CouplingAC
Voltage range±10mV to ±20V
Vertical resolution14 bits
Bandwidth0 – 60 MHz
Sampling rate125 MS/s or 62.5 MS/s
Memory depth32 MS per channel
Voltage reference measurement channel
Input connectorBNC female
Input impedance1MΩ
CouplingAC
Voltage range±10mV to ±20V
Vertical resolution14 bits
Bandwidth0 – 60 MHz
Sampling rate100 kS/s
Memory depth32 MS per channel
External protection module for PD channels
Overvoltage protection90 V (DC+AC peak)
Analog filterHigh-pass 16 kHz
Impedance adaptation50Ω
External protection module for VR channel
Overvoltage protection90 V (DC+AC peak)
Analog filterLow-pass 16 kHz
Impedance adaptation50Ω
External trigger input
Input connectorBNC female
Input impedance1MΩ
CouplingDC
Trigger typesEdge, pulse width, dropout, interval, logic
Threshold range±5 V DC coupled
Threshold accuracy±1% full scale*
Sensitivity200 mV p-p
Overvoltage protection±100 V (DC+AC peak)
Function generator
Output connectorBNC female
Output impedance50Ω
Output signalSine
Signal frequency0.025 Hz – 20 MHz
Frequency resolution< 0.025 Hz
Output voltage±2 V
Amplitude flatness< 1.5 dB to 20 MHz
DC accuracy±1% full scale*
Input supply
Power requirementsUSB 3.0 + DC adaptor / cable
Consumption6 W
Auxiliary transformer
Input connectorIEC 13
Input signal range220 VAC
Output connectorBNC male
Output signal12 VAC
Wave offset24°
General
PC connectivityUSB 3.0 SuperSpeed (USB 2.0 compatible)
Box dimensions190 × 170 × 40 mm
Weight< 0.5 kg
Storage temp-20 ºC to 60 ºC
Operating temp0 ºC to 40 ºC
Humidity5% to 80 %RH non-condensing
Environment2000 m altitude / EN61010 pollution degree 2
Safety approvalsEN 61010-1:2010
EMC approvalsEN61326-1:2013 / FCC Part 15 Subpart B
Environmental approvalsRoHS / WEEE compliant

TECHNICAL SPECIFICATIONS

Partial discharge measuring & others Function generator & others
Partial discharge measuring channels
Input connectorBNC female
Input impedance1MΩ
CouplingAC
Voltage range±10mV to ±20V
Vertical resolution14 bits
Bandwidth0 – 60 MHz
Sampling rate125 MS/s or 62.5 MS/s
Memory depth32 MS per channel
Voltage reference measurement channel
Input connectorBNC female
Input impedance1MΩ
CouplingAC
Voltage range±10mV to ±20V
Vertical resolution14 bits
Bandwidth0 – 60 MHz
Sampling rate100 kS/s
Memory depth32 MS per channel
External protection module for PD channels
Overvoltage protection90 V (DC+AC peak)
Analog filterHigh-pass 16 kHz
Impedance adaptation50Ω
External protection module for VR channel
Overvoltage protection90 V (DC+AC peak)
Analog filterLow-pass 16 kHz
Impedance adaptation50Ω
External trigger input
Input connectorBNC female
Input impedance1MΩ
CouplingDC
Trigger typesEdge, pulse width, dropout, interval, logic
Threshold range±5 V DC coupled
Threshold accuracy±1% full scale*
Sensitivity200 mV p-p
Overvoltage protection±100 V (DC+AC peak)
Function generator
Output connectorBNC female
Output impedance50Ω
Output signalSine
Signal frequency0.025 Hz – 20 MHz
Frequency resolution< 0.025 Hz
Output voltage±2 V
Amplitude flatness< 1.5 dB to 20 MHz
DC accuracy±1% full scale*
Input supply
Power requirementsUSB 3.0 + DC adaptor / cable
Consumption6 W
Auxiliary transformer
Input connectorIEC 13
Input signal range220 VAC
Output connectorBNC male
Output signal12 VAC
Wave offset24°
General
PC connectivityUSB 3.0 SuperSpeed (USB 2.0 compatible)
Box dimensions190 × 170 × 40 mm
Weight< 0.5 kg
Storage temp-20 ºC to 60 ºC
Operating temp0 ºC to 40 ºC
Humidity5% to 80 %RH non-condensing
Environment2000 m altitude / EN61010 pollution degree 2
Safety approvalsEN 61010-1:2010
EMC approvalsEN61326-1:2013 / FCC Part 15 Subpart B
Environmental approvalsRoHS / WEEE compliant
Partial discharge measurement channels Integrated processing functions
ConnectorFemale BNC
Impedance50 Ω
CouplingAC
Voltage rangesFrom ±5 mV to ±25 V
Vertical resolution14 bits
Bandwidth0 - 30 MHz
Sampling rate100 MS/s
Memory depth2 MS per channel
Surge protectionDischarger and disconnection
Analog filterHigh pass of 30 kHz / 1 MHz
Dynamic Range81 dB
Minimum pulse rise time3.5 ns
DP filteringDetection of discharges under the noise level by means of Wavelet filtering + statistical analysis
PD pulse waveform analysisExtraction of f, α and β parameters, for 3D clustering
Reference voltage waveform analysisExtraction of RMS value, frequency and offset of AC signal
Storage of capture parametersTrigger moment (system/GPS time), trigger type, armed result
GPS status storageUTC time, coverage, positioning mode, antenna position, self-survey
Communication networkRJ-45 / IEEE 802.3 / 10-1000 Fast/Gigabit Ethernet
SynchronizationMicroUSB, 20 cm cable, up to 9 units chain
VHF/UHF measurementTEV 30 MHz–1 GHz, Windowed/Invasive 100 MHz–2 GHz
LEDs2 indicators, RGB, Green/Yellow/Orange/Red
General systemWatchdog, non-volatile flash storage, SD 32 GB, RTC
Network functionsStatic/dynamic IP, UDP detect, remote server mode
Firmware updateJTAG / Remote FOTA
GroundingBy M3 screw on panel
Voltage reference measurement channel Synchronization / VHF/UHF / LEDs
ConnectorFemale BNC
Impedance1 MΩ
CouplingAC
Voltage range±220 mV ~ ±40 V
Vertical resolution12 bits
Bandwidth0–16 kHz
Sampling rate100 kS/s
Memory depth2 kS
Supported PD channelPD1 external coupler, PD2 integrated coupler
Type of sensorsTEV, Windowed, Invasive/Drain valve
Bandwidth30 MHz–1 GHz, 250–750 MHz, UHF 100 MHz–2 GHz
DC Output Voltage12 VDC (coupled)
Temperature & humidity sensors System / Network / Firmware
Connector typeTerminal, 0.05–1.3 mm²
Number of sensorsUp to 9
Supported sensorsNTC thermistor 10 kΩ
Max. cable length30 m
Humidity sensorAM2315C, I²C, cable 1.5 m
Auto recoveryWatchdog
Configuration storageNon-volatile flash
Monitoring dataSD card 32 GB
System timeRTC
IP ConfigurationStatic/dynamic
Current & Pressure sensors Power supply / General / Housing
Connector typeTerminal 0.05–1.3 mm²
Number of sensorsUp to 4
Sensor typeRogowski coil
Inner diameterUp to 94 cm
Nominal output100 mV/kA @ 50/60 Hz RMS
Max current100 kA
Integrator output0–10 VDC
Scale values100–5000 A configurable
ProtectionIP68
Pressure sensors2 max, transducer, 2-wire, 4–20 mA, 24 V
TriggerManual, edge, GPS, pre 16k×10ns, post 232×10ns
Power supply12–24 VDC / 12 VAC, 8 W
Storage temp.-20 to +70 °C
Operating temp.-10 to +50 °C
Internal sensors2 sensors internal temp.
HumidityUp to 90 %RH non-cond.
HousingIP65
Dimensions252 × 172 × 83 mm
Weight2.2 kg
TECHNICAL SPECIFICATIONS
Partial discharge measurement channels Integrated processing functions
ConnectorFemale BNC
Impedance50 Ω
CouplingAC
Voltage rangesFrom ±5 mV to ±25 V
Vertical resolution14 bits
Bandwidth0 - 30 MHz
Sampling rate100 MS/s
Memory Depth2 MS per channel
Surge protectionDischarger and disconnection
Analog filter
  • High pass of 30 kHz
  • High pass of 1 MHz
Dynamic Range81 dB
Minimum pulse rise time3.5 ns
DP filtering Detection of discharges under the noise level by means of Wavelet filtering + statistical analysis
PD pulse waveform analysis Extraction of f, α and β parameters, for 3D clustering
Reference voltage waveform analysis Extraction of the parameters RMS value, frequency and offset of the AC signal
Storage of capture parameters Trigger moment (system time and GPS time with optional module), trigger type, result of armed (correct/fail)
GPS status storage (optional module) UTC time, coverage values, positioning mode, antenna position, self-survey, etc…
Voltage reference measurement channel Communication network
ConnectorFemale BNC
Impedance1 MΩ
CouplingAC
Voltage rangeFrom ±220 mV to ±40 V
Vertical resolution12 bits
Bandwidth0 – 16 kHz
Sampling rate100 kS/s
Memory depth2 kS
Connector typeRJ-45
Communication ProtocolIEEE 802.3
Speed10/100/1000 Fast/Gigabit Ethernet
Type of cableRJ-45 8 pin
Temperature sensors Synchronization of multiple SmartVisor equipment
Connector typeTerminal connection with 0.05-1.3 mm² (16-30 AWG)
Number of sensorsUp to 9 sensors
Supported sensorsNTC thermistor with 10 kΩ
Maximum length of connection cableUp to 30 meters
Connector typeMicroUSB
Type of cable20 cm microUSB cable
Maximum number of units in a chainUp to 9 units - 18 simultaneous PD channels
Temperature and humidity sensor VHF/UHF measurement with UHF-CO2 converter
Connector typeTerminal connection with 0.05-1.3 mm² (16-30 AWG)
Number of sensors1 sensor
Supported sensorAM2315C
Communication interfaceI2C
Maximum length of connection cableUp to 1.5 meters
Supported PD channel
  • PD1: Using external VDC coupler
  • PD2: Integrated coupler activatable in channel
Type of sensorsTEV, Windowed, Invasive / Drain Valve
Bandwidth
  • TEV: VHF/UHF 30 MHz to 1 GHz, 250–750 MHz with band-pass filter for UHF band
  • Windowed/Invasive: UHF 100 MHz – 2 GHz
DC Output Voltage12 VDC (coupled in measurement)
Current sensors Leds indicators
Connector typeTerminal connection with 0.05-1.3 mm² (16-30 AWG)
Number of sensorsUp to 4 sensors
Sensor typeRogowski coil
Inner diameterUp to 94 cm
Nominal coil output rate100 mV / kA @ 50/60 Hz (RMS)
Maximum measurable current100 kA
Integrator output0 to 10 VDC
Total scale values Configurable in amps: 100, 200, 300, 400, 500, 600, 800, 1000, 1500, 2000, 2500, 4000, 5000
Degree of protectionIP68
Number of indicatorsTwo, status and diagnostic
LED TypeRGB
Color RangeGreen/Yellow/Orange/Red
Indication typeFixed and blinking light
Pressure sensors General system functions
Connector typeTerminal connection with 0.05-1.3 mm² (16-30 AWG)
Number of sensorsUp to 2 sensors
Sensor typeTransducer
Connection2-wire interface
Analog output4 to 20 mA
Additional power supply24 V
Auto recoveryWatchdog
Configuration storageNon-volatile flash memory storage
Monitoring data storageSD card with 32 GB
System timeReal time clock
Advanced trigger function Network functions
Trigger conditions
  • Manual trigger
  • Per level (edge/level)
  • PPS of GPS (optional module)
Pre-trigger16000 samples of 10 ns
Post-triggerUp to 232 samples of 10 ns
IP ConfigurationStatic or dynamic IP
Integrated network services
  • Detection of network equipment by UDP
  • Reception of control connections
  • Send data to remote server in autonomous mode
Firmware update interface
 
Local programmingJTAG Connection
Remote programmingFOTA Remote Update App
Grounding
 
GroundingBy M3 screw on panel
Power supply
 
Connector typeTerminal connection with 0.05-3.3 mm² (12-30 AWG)
Voltage range12-24 VDC / 12 VAC
Consumption8 W
General
 
Storage temperatureFrom -20 to +70 ºC
Operating temperatureFrom -10 to +50 ºC
Internal temperature sensors2 sensors for reading internal temperature values on equipment
Humidity rangeUp to 90 %RH non-condensing
Housing
 
Dimensions128 x 210 x 34 mm
Weight0.8 kg
AccessoriesDIN Rail Connector
IP CodeIP50
TECHNICAL SPECIFICATIONS
Partial discharge measurement channels Integrated processing functions
ConnectorFemale BNC
Impedance50 Ω
CouplingAC
Voltage rangesFrom ±5 mV to ±25 V
Vertical resolution14 bits
Bandwidth0 - 30 MHz
Sampling rate100 MS/s
Memory Depth2 MS per channel
Surge protectionDischarger and disconnection
Analog filterHigh pass of 30 kHz / High pass of 1 MHz
Dynamic Range81 dB
Minimum pulse rise time3.5 ns
DP filteringDetection of discharges under noise level using Wavelet filtering + statistical analysis
PD pulse waveform analysisExtraction of f, α, β parameters (3D clustering)
Reference voltage waveform analysisExtraction of RMS value, frequency, offset
Storage of capture parametersTrigger moment (system & GPS), type, armed result
GPS status storageUTC time, coverage, positioning mode, antenna, self-survey
Voltage reference measurement channel Communication network
ConnectorFemale BNC
Impedance1 MΩ
CouplingAC
Voltage rangeFrom ±220 mV to ±40 V
Vertical resolution12 bits
Bandwidth0 – 16 kHz
Sampling rate100 kS/s
Memory depth2 kS
Connector typeRJ-45
ProtocolIEEE 802.3
Speed10/100/1000 Fast/Gigabit Ethernet
CableRJ-45 8 pin
Temperature sensors Synchronization of multiple SmartVisor equipment
Connector typeTerminal (0.05-1.3 mm2 / 16-30 AWG)
Number of sensorsUp to 9 sensors
Supported sensorsNTC thermistor 10 kΩ
Max cable lengthUp to 30 m
ConnectorMicroUSB
Cable20 cm microUSB cable
Max unitsUp to 9 (18 PD channels)